Link-systems Max Presence Sensing Device Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Instrumentos de medida Link-systems Max Presence Sensing Device. LINK Systems Max Presence Sensing Device User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 48
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
Black Max
MANUAL
INCLUDES
SECTIONS
1,3, &4
Link Lite 305
Black Max
User Requirements
Installation Information
Operating Instructions
LINK ELECTRIC & SAFETY CONTROL COMPANY
444 McNALLY DRIVE, NASHVILLE TN 37211
PH (615)-833-4168 FAX (615)-834-1984
Vista de página 0
1 2 3 4 5 6 ... 47 48

Resumo do Conteúdo

Página 1 - Black Max

Black MaxMANUALINCLUDESSECTIONS1,3, &4Link Lite 305Black MaxUser RequirementsInstallation InformationOperating InstructionsLINK ELECTRIC & SAF

Página 2

Link Lite Black Max Section 3 - Installation3-5When no stopping performance monitor isused on a machine (you must use one whenrequired by OSHA or ANSI

Página 3

Link Lite Black Max Section 3 - Installation3-63. The mounting location or method mustleave access for work pieces, tool changes,and other operationa

Página 4

Link Lite Black Max Section 3 - Installation3-78. The Black Max transmitter and receivereach have four mounting holes, two in eachend mounting flange

Página 5

Link Lite Black Max Section 3 - Installation3-8Figure 3.7. Shows remote segment unitsmounted on a straight side press withcolumns extended beyond the

Página 6

Link Lite Black Max Section 3 - Installation3-9Also, the mounting arrangement is some-what different for the remote segement unitsas shown in Figures

Página 7

Link Lite Black Max Section 3 - Installation3-10Figure 3.12 Illustrates a four sided perime-ter guarding application.Figure 3.12: Top view of four si

Página 8

Link Lite Black Max Section 3 - Installation3-11Figure 3.13: Location of transmitter power connector.

Página 9

Link Lite Black Max Section 3 - Installation3-12Unplug the terminal/connector from itssocket and turn the three wire clampscrews counterclockwise so t

Página 10

Link Lite Black Max Section 3 - Installation3-13Figure 3.14: Power and relay connections for Black Max receiver.

Página 11

Link Lite Black Max Section 3 - Installation3-14paths in special interfaces between theBlack Max and the machine controlsdesigned by Link Systems.Link

Página 12

Link Lite Black Max Section 1 - User Requirements1-11. IMPORTANT REQUIREMENTSAND RESPONSIBILITIES THATTHE USER/EMPLOYER MUSTMEET WHEN USING LINK LITEB

Página 13

Link Lite Black Max Section 3 - Installation3-15Figure 3.15: Location of relay check con-figuration jumpers.

Página 14

Link Lite Black Max Section 3 - Installation3-16shown in Figure 3.15 will configure therelay cycle circuit for 115VAC inputvoltage between terminals 1

Página 15

Link Lite Black Max Section 3 - Installation3-17Figure 3.16: Use of remote segment at bottom of main transmitter.

Página 16 - Figure 3.13:

Link Lite Black Max Section 3 - Installation3-18Figure 3.17: Remote segment unit used at top of main transmitter.

Página 17

Link Lite Black Max Section 3 - Installation3-19Figure 3.18: Use of two remote segment units with main transmitter.

Página 18 - Figure 3.14:

Link Lite Black Max Section 3 - Installation3-20Figure 3.19: Location of the transmitter power level switch and power level table.

Página 19

Link Lite Black Max Section 3 - Installation3-21NOTE! The receiver unit of the BlackMax light curtain is designed to supply astop signal when far too

Página 20

Link Lite Black Max Section 3 - Installation3-22sent by the Black Max receiver unit to themachine control.Figure 3.22a: Transmitter and receiver outof

Página 21

Link Lite Black Max Section 3 - Installation3-23brackets (or surface) to which the transmit-ter and receiver are to be mounted are inreasonable alignm

Página 22

Link Lite Black Max Section 3 - Installation3-24Perform the following checkout steps:1. Turn on power to the Link Lite BlackMax units by turning the

Página 23 - Figure 3.17:

Link Lite Black Max Section 1 - User Requirements1-25.Machine controls must be designed for"Control Reliability", i.e., so that a singlefail

Página 24

Link Lite Black Max Section 3 - Installation3-259. Take the test bar or strip used in steps 4through 6 and insert it into the sensing fieldbetween th

Página 25

Link Lite Black Max Section 3 - Installation3-26have a body part in the hazardous areawithout being detected. If remote segmentBlack Max units are no

Página 26

Link Lite Black Max Section 3 - Installation3-27Figure 3.23: Illustration of barriers installed to prevent someone from reaching overthe top of a Blac

Página 27

Link Lite Black Max Section 3 - Installation3-28Figure 3.24: A Black Max with supplemental barrier to prevent standingbetween light curtain and hazard

Página 28

Link Lite Black Max Section 4 - Operating Instructions4-14 OPERATING INSTRUCTIONS,REQUIREMENTS, AND PRECAU-TIONSIMPORTANT! All setup personnel,ope

Página 29

Link Lite Black Max Section 4 - Operating Instructions4-22. The main Black Max sensing field mustbe located far enough away from thehazardous area th

Página 30

Link Lite Black Max Section 4 - Operating Instructions4-3required to prevent someone from reachingthe hazardous area from any normalposition associate

Página 31

Link Lite Black Max Section 4 - Operating Instructions4-4When muting is used, it must be checkedfor proper adjustment each time mainte-nance is perfor

Página 32 - Figure 3.23:

Link Lite Black Max Section 4 - Operating Instructions4-5NOTE! The Black Max always gives astop signal unless the blanking modeselector switch is in

Página 33

Link Lite Black Max Section 4 - Operating Instructions4-6NOTE! When FIXED BLANKING isused, removal of the object(s) that blocksthe transmitter light

Página 34

Link Lite Black Max Section 1 - User Requirements1-32.The specific duties and actions to beperformed by setup and operator personnelfor each job relat

Página 35

Link Lite Black Max Section 4 - Operating Instructions4-74.2.4 Requirements for Safe Use ofBlankingSince blanking leaves "windows" in the

Página 36

Link Lite Black Max Section 4 - Operating Instructions4-84.3 Safety System SetupEach time a machine or production systemis set up with new tooling

Página 37

Link Lite Black Max Section 4 - Operating Instructions4-9step 2. If they are on, have an authorizedperson use the RUN/PROGRAM/SELECTswitch to turn th

Página 38

Link Lite Black Max Section 4 - Operating Instructions4-10scribed in section 3.8 of this manual mustbe performed before placing the machineback into p

Página 44

Link Lite Black Max Section 1 - User Requirements1-4Where a production system uses auxiliaryequipment for scrap chopping, materialfeeding, part remova

Página 45

Link Lite Black Max Section 3 - Installation3-13 INSTALLATION3.1 General RequirementsBoth OSHA and ANSI standards make itthe user/employer's re

Página 46

Link Lite Black Max Section 3 - Installation3-2selected by the user/employer to install thebarriers must:1.Determine where barriers arenecessary and t

Página 47

Link Lite Black Max Section 3 - Installation3-3Ts = the stop time (in seconds) of themachine measured from the controloutput stop signal to the actuat

Página 48

Link Lite Black Max Section 3 - Installation3-4following formula. Use this formula onlyfor M.O.S. less than 2.75 inches.Dpf = 3.4 (M.O.S. - .276)Figu